Configured device differs from real device
Kuka · ProfiNet Controller/Device 3.1
Was bedeutet 11007 ?
The PROFINET device configured in the controller's software does not match the actual physical device connected at the specified Slot and Subslot for {Name}. This configuration discrepancy prevents correct communication and operation of the device.
Häufige Ursachen
- The configured device parameters do not match the actual device.
- Configuration file loaded into the PLC is for a different hardware model or revision.
- Device has been replaced or its configuration changed without updating the PLC.
- Incorrect device identification during network scan.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Compare the configured device type and model in WorkVisual for device {Name} at Slot {Slot}, Subslot {Subslot} with the actual device nameplate information.
- 2
Update the PROFINET configuration in WorkVisual to precisely match the physically connected device's identity at the specified slot and subslot.
- 3
Ensure the GSDML file used for device {Name} in the PROFINET project is the correct version for the installed hardware.