Übersetzen...
13037

Profinet controller stack cannot be started

Kuka · ProfiNet Controller/Device 3.1

Was bedeutet 13037 ?

The PROFINET controller stack failed to start. The root cause is an incorrect parameterization of the PROFINET firmware, specifically an issue within the 'bas_cm_api.xml' configuration file. This prevents the robot controller from acting as a PROFINET controller.

Häufige Ursachen

  • The Profinet controller stack failed to start.
  • Initialization error within the Profinet communication software.
  • Missing or corrupted Profinet configuration files.
  • Insufficient system resources to run the Profinet controller.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Review the parameterization settings for the PROFINET firmware by examining the contents of the 'bas_cm_api.xml' file.

  2. 2

    Verify that all required parameters within 'bas_cm_api.xml' are correctly configured according to the PROFINET specifications.

  3. 3

    Compare the 'bas_cm_api.xml' file with a known good backup or reference configuration for correct structure and values.

Alle Codes in diesem Handbuch durchsuchen (13)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Kuka ProfiNet Controller/Device 3.1