Übersetzen...
012

OC2

Lenze · 9300 Series

Was bedeutet 012 ?

One of the motor phases has made contact with earth (ground), indicating an earth fault. This suggests an insulation breakdown in the motor cable or the motor windings.

Häufige Ursachen

  • Insulation breakdown in the motor cable due to mechanical stress (chafing, crushing) or chemical/moisture ingress.
  • Internal short circuit or insulation failure within motor windings, often caused by overheating, contamination, or age.
  • Improper grounding of the motor frame or drive enclosure, creating an unintended current path to earth.
  • Accumulation of conductive dust, metal particles, or moisture on motor terminals or inside the terminal box, bridging phases to ground.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Disconnect the motor power cables (U, V, W) from the drive's output terminals.

  2. 2

    2. Using a megohmmeter (insulation resistance tester), measure insulation resistance between each motor phase (U, V, W) and the motor frame ground terminal. A reading below 1 Megohm (1MΩ) indicates a fault.

  3. 3

    3. If motor insulation is good, measure insulation resistance between each conductor of the motor cable and the cable shield/earth conductor.

  4. 4

    4. Visually inspect the motor cable along its entire length for signs of damage (cuts, abrasions, crushing) and check the motor terminal box for moisture or debris.

  5. 5

    5. If a cable or motor winding fault is confirmed, isolate the faulty component for repair or replacement.

Alle Codes in diesem Handbuch durchsuchen (145)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes