Übersetzen...
015

OC5

Lenze · 9300 Series

Was bedeutet 015 ?

The drive is experiencing an I x t overload, characterized by frequent and excessively long acceleration phases with overcurrent, or continuous overload where Imotor > 1.05 x Irx. This indicates that the drive is undersized for the application.

Häufige Ursachen

  • Load inertia is too high for the motor/drive combination, causing extended acceleration times with excessive current.
  • Mechanical binding, increased friction, or a seized component in the driven equipment, requiring higher starting torque.
  • Drive acceleration time (e.g., Parameter C0026) is set too short, leading to rapid current increase and an Ixt trip.
  • Motor rated current (e.g., Parameter C0020) is set incorrectly or lower than the actual motor nameplate current.
  • Continuous operation where Imotor > 1.05 x Irx, indicating the drive is undersized for the application's continuous demand.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Monitor the actual motor current (via drive display or clamp meter) during acceleration and steady-state operation, comparing it to the drive's rated output current (Irx).

  2. 2

    2. Increase the drive's acceleration time (e.g., Parameter C0026) in small increments (e.g., 0.5-1.0 seconds) and observe the fault frequency.

  3. 3

    3. Verify that the motor rated current (Parameter C0020) and motor nominal frequency (Parameter C0022) in the drive parameters match the motor nameplate data.

  4. 4

    4. Mechanically disengage the motor from the load (if safe) and run the motor unloaded to check for drive current anomalies and reduce mechanical influence.

  5. 5

    5. Inspect the mechanical system (bearings, gearboxes, belts) for signs of binding, wear, or excessive friction that would increase load.

Alle Codes in diesem Handbuch durchsuchen (145)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026