NMAX Maximum speed exceeded
Lenze · 9300 Series
Was bedeutet 0200 ?
The motor speed has exceeded the maximum limit defined in parameter C0596. This indicates an overspeed condition potentially due to incorrect parameter settings, external load conditions, or control system malfunction.
Häufige Ursachen
- Parameter C0596 (Maximum motor speed) set incorrectly to a value lower than the actual commanded speed or the motor's mechanical limit.
- Malfunction in the speed feedback system (e.g., encoder, resolver) providing an erroneous high-speed signal to the drive.
- External mechanical load overdriving the motor (e.g., gravity load on a hoist, runaway conveyor), exceeding its commanded speed.
- Instability or incorrect tuning of the speed controller (e.g., C0026, C0027) causing oscillations that momentarily exceed the speed limit.
- Incorrect scaling of the analog speed reference input (e.g., X3/AI1, X3/AI2) or digital speed reference, leading to an unintended high-speed command.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify the setting of parameter C0596 (Maximum motor speed) and ensure it is appropriate for the motor and application, and not set too low.
- 2
Compare the drive's reported motor speed (e.g., via diagnostic display C0002) with an independent measurement (e.g., tachometer on motor shaft).
- 3
Check the wiring and integrity of the speed feedback device (encoder/resolver) connected to terminals X8/1 to X8/10 for damage or noise.
- 4
Review the control system's speed command source (e.g., analog input, fieldbus, keypad) and verify its scaling and maximum output value.
- 5
If an external load can overdrive the motor, consider implementing mechanical braking or a regenerative braking solution to manage overspeed conditions.
- 6
Check speed controller gains (e.g., C0026, C0027) for stability, performing an autotuning routine (C0004=1) if available and safe to do so.