Übersetzen...
073

PR2

Lenze · 9300 Series

Was bedeutet 073 ?

A checksum error was detected in parameter set 2 during loading or transfer via the keypad. This indicates a fault in the parameter data or incompatibility with the loaded software version. The Lenze default settings are loaded automatically.

Häufige Ursachen

  • Corrupted parameter data: The parameter data being loaded (e.g., from a keypad, memory module, or communication interface) for parameter set 2 is corrupted during transmission or storage.
  • Incompatible firmware/software: The parameter set 2 saved in the keypad or external memory was created with a different firmware version of the device, leading to data structure mismatch.
  • Keypad malfunction: The keypad itself has an internal fault, causing incorrect data to be written or read for parameter set 2, resulting in a checksum mismatch.
  • Power interruption during write: Power supply fluctuation or interruption occurred precisely while parameter set 2 was being written to non-volatile memory.
  • Internal memory corruption: A rare internal fault in the device's non-volatile memory (e.g., EEPROM or Flash) where parameter set 2 is stored.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Re-attempt to load parameter set 2, ensuring a stable power supply and observing for any communication errors during the process.

  2. 2

    Try loading the factory default parameter set (e.g., using parameter P0-10 = 100) and then manually re-enter critical parameters for set 2 to confirm data storage integrity.

  3. 3

    If loading from an external keypad or module, try using a different, known-good keypad/module to eliminate the possibility of a hardware fault.

  4. 4

    If available, upgrade the device firmware to the latest compatible version (refer to manufacturer's documentation) and then try loading parameter set 2 again.

  5. 5

    Backup existing parameters (if possible) and perform a full device reset (e.g., P0-10 = 100 or P0-10 = 110 for complete factory reset) before attempting to reload parameter set 2.

Alle Codes in diesem Handbuch durchsuchen (145)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes