Übersetzen...
083

Sd3

Lenze · 9300 Series

Was bedeutet 083 ?

An encoder error has occurred at terminal X9, typically due to an interrupted encoder cable or pin X9/8 not being connected. This can lead to incorrect or no position feedback.

Häufige Ursachen

  • Open circuit or damaged conductor in the encoder feedback cable connected to terminal X9.
  • Pin X9/8 (typically encoder power supply return or ground) is not connected or has a high resistance connection.
  • Incorrect encoder wiring to terminal X9 (e.g., swapped A/B signals, missing power supply, shield fault).
  • Faulty encoder sensor (e.g., mechanical damage, internal electronics failure) providing no or intermittent signals.
  • Loose or corroded connections at the encoder connector, terminal X9 on the drive, or intermediate junction boxes.
  • Insufficient or excessive encoder supply voltage (e.g., 5V or 24V) provided by the drive or external supply.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Power down and lockout the drive. Disconnect the encoder cable from terminal X9 on the drive and at the encoder end.

  2. 2

    2. Using a multimeter, check continuity of each individual wire in the encoder cable, paying special attention to the conductor for pin X9/8.

  3. 3

    3. Verify the encoder supply voltage (e.g., 5VDC or 24VDC) present at terminal X9/7 and X9/8 with reference to ground, when the drive is powered on (motor disconnected).

  4. 4

    4. Inspect terminal X9 on the drive and the encoder connector for bent pins, corrosion, or loose connections.

  5. 5

    5. Ensure the encoder cable shield is properly connected to the drive's designated ground terminal (PE) at X9 and the encoder housing.

Alle Codes in diesem Handbuch durchsuchen (145)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes