Übersetzen...
107

H07

Lenze · 9300 Series

Was bedeutet 107 ?

An internal fault related to the power stage has occurred. During the initialisation of the controller, an incorrect power stage was detected, indicating a serious internal hardware issue.

Häufige Ursachen

  • Internal power stage component failure (e.g., IGBT module, gate driver circuit) due to overstress or manufacturing defect.
  • Internal communication bus error between the control board and power board during the drive's boot-up sequence.
  • Faulty or corrupted power stage identification hardware (e.g., EEPROM, configuration resistors) preventing correct recognition.
  • Transient voltage event or brownout during controller initialization causing an incorrect detection of the installed power stage.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Power cycle the drive and observe if the internal fault clears upon re-initialization.

  2. 2

    2. Measure incoming AC line voltage (L1, L2, L3 or L, N) at the drive's input terminals and confirm it is within specified tolerance (e.g., 380-480VAC +/-10%).

  3. 3

    3. Disconnect the motor and any external braking resistor from the drive. Power cycle the drive and check if the fault persists (to isolate external loads).

  4. 4

    4. If the drive is modular, ensure all internal power and control module connections are securely seated.

  5. 5

    5. Contact the drive manufacturer's technical support, providing the exact fault code and drive serial number for internal component diagnosis.

Alle Codes in diesem Handbuch durchsuchen (145)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Lenze 107 (H07) — Technische Referenz | ErrorLib