Übersetzen...
OC1

Overcurrent during DC-injection braking

Lenze · 9300 Series

Was bedeutet OC1 ?

An overcurrent (OC1) TRIP occurs if, during DC-injection braking (GSB) at high motor speeds, the residual voltage from magnetism and high speed generates an excessive motor current. This happens because the pulse inhibit (DCTRL-IMP) set during braking is too short.

Häufige Ursachen

  • DC injection braking activated at too high a motor speed (P0-03), generating excessive back EMF that combines with the injected DC current.
  • Parameter C0201 (DC-Injection Braking Enable) or C0202 (DC-Injection Braking Current) configured inappropriately for the motor or application.
  • Braking ramp time (P1-10) set too short, forcing rapid deceleration and high regenerative energy during the transition to DC braking.
  • Motor's residual magnetism or inertia causing high generated voltage when DC braking is initiated, leading to overcurrent.
  • Drive hardware fault in the output stage leading to uncontrolled current during DC injection braking.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Adjust parameter C0201 (DC-Injection Braking Enable) to ensure DC braking is only initiated below a safe motor speed threshold (P0-03).

  2. 2

    2. Reduce parameter C0202 (DC-Injection Braking Current) to a lower value, then gradually increase while monitoring motor current (P0-04).

  3. 3

    3. Increase the deceleration ramp time (P1-10) to allow the motor speed (P0-03) to decay sufficiently before DC braking engages.

  4. 4

    4. Verify the motor's rated current (P2-03) and ensure C0202 does not exceed this value or the drive's capabilities.

  5. 5

    5. Check for external load conditions that might be driving the motor during deceleration, increasing its speed before DC braking.

Alle Codes in diesem Handbuch durchsuchen (145)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026