Übersetzen...
x091

EEr External monitoring (activated via DCTRL)

Lenze · 9300 Series

Was bedeutet x091 ?

An external monitoring function has triggered this fault, which is activated via DCTRL (Drive Control) and configured through parameter C0581. The 'x' in the code indicates the response type: 0 for TRIP, 1 for message, 2 for warning.

Häufige Ursachen

  • The external safety circuit (e.g., E-Stop, light curtain, guard door switch) connected to a digital input configured for external monitoring has opened.
  • A signal on a digital input configured as an external fault input via parameter C0581 has changed state, triggering the fault.
  • Wiring fault (e.g., broken wire, short circuit) in the external monitoring circuit connected to the drive.
  • External PLC or control system outputting an incorrect signal to the drive's external monitoring input.
  • Incorrect configuration of parameter C0581, where a normally closed contact is expected but an open contact is provided.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Identify the specific digital input assigned as the external monitoring input via parameter C0581 and measure its voltage state.

  2. 2

    Trace the wiring from the identified digital input to the external monitoring device (e.g., E-stop button, safety relay contact).

  3. 3

    Verify the status of all external safety devices and ensure their contacts are closed (or open, as configured) as expected.

  4. 4

    Check the logic configured in parameter C0581 (e.g., active high or active low) and ensure it matches the external signal.

  5. 5

    Perform a continuity test on the external monitoring circuit wiring to identify any breaks or short circuits.

Alle Codes in diesem Handbuch durchsuchen (145)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes