Übersetzen...
28802

Analog input 2 fault

Lenze · i550 Protec Drive

Was bedeutet 28802 ?

The monitoring function for analog input 2 has been triggered, as configured via parameters 0x2637:008 (P431.08) and 0x2637:009 (P431.09). This indicates an issue with the signal connected to analog input 2, potentially an out-of-range or missing signal.

Häufige Ursachen

  • Analog input signal from the external device connected to Analog Input 2 is outside the configured monitoring range (P431.08, P431.09).
  • Cable fault (open circuit or short circuit) in the wiring connected to Analog Input 2, resulting in an invalid signal level.
  • Malfunctioning external sensor (e.g., potentiometer, temperature probe) providing an out-of-specification signal.
  • Misconfiguration of the monitoring thresholds in parameters 0x2637:008 (P431.08) and 0x2637:009 (P431.09).
  • Electromagnetic interference (EMI) or ground loop issues affecting the signal integrity on Analog Input 2.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the actual signal voltage or current at the Analog Input 2 terminals (e.g., X3.3, X3.4) to confirm its value.

  2. 2

    Check the output of the sensor or transducer connected to Analog Input 2 directly at its terminals for expected signal levels.

  3. 3

    Verify the wiring continuity and shielding from the sensor to Analog Input 2 for damage or loose connections.

  4. 4

    Review parameters 0x2637:008 (P431.08) and 0x2637:009 (P431.09) to ensure they are appropriate for the expected signal range.

  5. 5

    Disconnect the external signal and apply a known test voltage or current to Analog Input 2 to check the drive's input circuit functionality.

Alle Codes in diesem Handbuch durchsuchen (52)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Lenze 28802 (Analog input 2 fault) — Technische Referenz | ErrorLib