E.GF
Output side ground fault overcurrent protection
Mitsubishi Electric · A500 Inverter
Was bedeutet E.GF ?
This function stops the inverter output if a ground fault overcurrent flows due to a ground fault occurring in the inverter's output side (load side). This indicates an insulation breakdown in the motor or the cable connecting the inverter to the motor.
Häufige Ursachen
- Excessive current flowing to ground from the motor or inverter output.
- Damaged motor insulation leading to a ground fault.
- Short circuit between a power conductor and the unit's chassis.
- Faulty inverter power module allowing leakage current.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Perform an insulation resistance test (megger test) between each motor output phase (U, V, W) and the motor frame ground.
- 2
Perform an insulation resistance test between each conductor of the connection cable and ground.
- 3
Visually inspect the motor and cable for any signs of physical damage or insulation breakdown.