E56

Power Transistor Thermistor Faulty or Disconnected

Mitsubishi Electric · FR-D700 Inverter

Was bedeutet E56 ?

The power transistor thermistor is faulty or disconnected (specific to FDCVA151-251 models), impacting temperature monitoring of the power transistors. This can lead to inverter damage from overheating.

Häufige Ursachen

  • Disconnection of the power transistor thermistor.
  • Open circuit fault in the power transistor thermistor sensor.
  • Faulty power transistor thermistor indicating an incorrect temperature.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Inspect the power transistor thermistor connection for dislodgement or damage, particularly on FDCVA151-251 models.

  2. 2

    Measure the resistance of the thermistor to verify functionality and compare to the specified temperature-resistance chart.

  3. 3

    Ensure the thermistor is securely connected to the inverter PCB and properly seated for accurate temperature sensing.