Stedy Spd OC

Overcurrent shut-off during constant speed

Mitsubishi Electric · FR-E500 Inverter

Was bedeutet Stedy Spd OC ?

The inverter output is shut off because the output current reached or exceeded approximately 200% of the rated current while operating at a constant speed. This suggests a sudden increase in load or a fault in the motor/wiring during stable operation.

Häufige Ursachen

  • Sudden, unexpected increase in mechanical load on the motor.
  • Output short-circuit or ground fault occurring during constant speed operation.
  • Motor experiencing mechanical binding or resistance during operation.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Monitor the motor's mechanical load for sudden changes or spikes during constant speed operation.

  2. 2

    Measure the motor load current during constant speed and compare it to the motor nameplate rated current.

  3. 3

    Inspect motor cable and motor terminals for signs of short-circuit or ground fault.