1401H

Input Dark Test Error

Mitsubishi Electric · MELSEC iQ-R I/O Module

Was bedeutet 1401H ?

During an input dark test, the module failed to detect the expected test pulses. This indicates a problem with the input dark test setup, the input wiring, the connected devices, or an unused input terminal that has not been correctly configured to be 'Not used'.

Häufige Ursachen

  • Expected test pulses were not detected during an input dark test, possibly due to wiring or device issues.
  • An unused input terminal is not correctly set to 'Not used' for 'Wiring input selection', interfering with the dark test.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    For any unused input terminals, set 'Wiring input selection' to 'Not used'.

  2. 2

    Check for the specific input terminal with the error using Input dark test error detection state (Un\G1040).

  3. 3

    Review and adjust the connected devices and wiring for the identified problematic input terminal.