Übersetzen...
2003H

Output dark test error

Mitsubishi Electric · MELSEC iQ-R I/O Module

Was bedeutet 2003H ?

During an output dark test, the expected test pulses were not detected. This signifies that the output circuit did not respond correctly to a diagnostic test, potentially due to wiring faults, issues with connected devices, or an internal hardware problem.

Häufige Ursachen

  • An unused output terminal is not configured with 'Not used' in 'Wiring output selection'.
  • Faulty connected devices or incorrect wiring on the output terminal.
  • Influence from electrical noise affecting the output dark test pulses.
  • An internal hardware error within the I/O module with diagnostic functions.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    For any unused output terminals, ensure 'Not used' is selected for 'Wiring output selection'.

  2. 2

    Identify the specific terminal experiencing the error using 'Output dark test error detection state' (Un\G1540), then inspect and adjust connected devices and wiring.

  3. 3

    Implement measures to mitigate electrical noise, such as shielding cables or isolating power supplies.

  4. 4

    If the error persists after noise mitigation, the module may require replacement due to a hardware failure.

Alle Codes in diesem Handbuch durchsuchen (56)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Mitsubishi Electric MELSEC iQ-R I/O Module