Übersetzen...
SIMULTANEOUS-OUTPUT-ON

Simultaneous Output ON (Source Type)

Mitsubishi Electric · MELSEC iQ-R I/O Module

Was bedeutet SIMULTANEOUS-OUTPUT-ON ?

When one output of a transistor output (source type) module is turned on, other loads connected to different outputs simultaneously turn on. This fault arises from a non-connection or disconnection between the external power supply 0V and the common line of the load, allowing current to flow through parasitic circuits in the off-state output elements. Continuous operation under this condition can lead to module failure.

Häufige Ursachen

  • Non-connection or disconnection between the external power supply 0V and the common line of the load.
  • Current flowing through parasitic circuits within the off-state output elements of the transistor output (source type) module.
  • Incorrect wiring configuration where common lines are not properly referenced to the external power supply 0V.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Correctly connect the external power supply and the load, ensuring the 0V and common lines are securely and properly connected.

  2. 2

    To prevent further occurrences, insert diodes at each output terminal to block parasitic current paths and isolate the outputs from unintended activation.

Alle Codes in diesem Handbuch durchsuchen (56)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Mitsubishi Electric MELSEC iQ-R I/O Module
Mitsubishi Electric SIMULTANEOUS-OUTPUT-ON — Diagnose & Res… | ErrorLib