TRIAC-LKG-C1

Triac Output Leakage Current (Surge Suppressor)

Mitsubishi Electric · MELSEC iQ-R I/O Module

Was bedeutet TRIAC-LKG-C1 ?

The triac output load fails to turn off due to a leakage current flowing through the triac module's built-in surge suppressor. This leakage current is significant enough to partially or fully energize the load, preventing it from deactivating completely when the output is commanded OFF.

Häufige Ursachen

  • Leakage current originating from the triac module's built-in surge suppressor.
  • Increased line capacitance due to long wiring distances between the output module and the load, exacerbating leakage current effects.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Connect a resistor in parallel across the load terminals. This resistor provides an alternative path for the leakage current, ensuring the load completely turns off.