CPU Down Error with Device Access Issue
Mitsubishi Electric · MELSEC System Q/L Series
Was bedeutet 1001 ?
The CPU module has experienced a runaway condition or failure, potentially due to electrical noise, a hardware fault, or (for Universal model QCPU) accessing outlying devices with device range checks disabled (SM237 = 1) during BMOV, FMOV, or DFMOV instruction execution. This error specifically affects QCPU and LCPU modules.
Häufige Ursachen
- Runaway or failure of CPU module.
- Malfunctioning due to noise or other external reasons.
- Hardware fault within the CPU module.
- Universal model QCPU accessed outlying devices with device range checks disabled (SM237 = 1) during BMOV, FMOV, or DFMOV instruction execution.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Implement noise reduction measures for the control system environment.
- 2
Reset the CPU module and attempt to RUN it again.
- 3
If the same error is displayed again after resetting, diagnose for a CPU module hardware fault.
- 4
For Universal model QCPU, check devices specified by BMOV, FMOV, and DFMOV instructions and correct device settings.