Ud (100)

Overheat Protection (Outdoor Pipe)

Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit

Was bedeutet Ud (100) ?

The outdoor pipe thermistor (TH2) detects a temperature of 70°C [158°F] or more during compressor operation. This indicates either a defective outdoor fan (fan motor), a short cycle of the outdoor unit during cooling operation, or a faulty outdoor pipe thermistor (TH2).

Häufige Ursachen

  • Outdoor pipe temperature has exceeded the overheat protection threshold (Ud code).
  • Insufficient refrigerant flow causing localized overheating.
  • Blockage in the outdoor unit's heat exchanger or piping.
  • Ambient temperature is too high, leading to poor heat dissipation.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the outdoor unit air passage for obstructions.

  2. 2

    Turn the power off and on again to clear the error code. If U9 is subsequently displayed, follow the U9 troubleshooting procedures.