Übersetzen...
E32
Phase Reversal or L2 Open Phase
Mitsubishi Electric · R410A Systems
Was bedeutet E32 ?
The anti-phase device has detected an incorrect phase sequence (requiring two phases to be swapped) or an open circuit in the L2 phase of the main power supply (specifically on the primary side of the contactor). This can lead to motor damage.
Häufige Ursachen
- Power supply phase imbalance detected.
- Loss of power on the L2 phase of the 3-phase supply.
- Faulty wiring or loose connection on L2.
- Overcurrent protection tripped due to phase issue.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify phase rotation of the incoming 3-phase power supply at the main terminals using a phase rotation meter.
- 2
Measure voltage between L1-L2, L2-L3, and L3-L1 on the primary side of the main contactor — expect balanced 3-phase voltage.
- 3
Check the main contactor's L2 terminal for secure connection and proper operation.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: Mitsubishi Electric R410A Systems