U3
Discharge Thermistor Short/Open
Mitsubishi Electric · R410A Systems
Was bedeutet U3 ?
The compressor discharge thermistor, which monitors compressor discharge temperature, is detected as either short-circuited or open-circuited. This prevents accurate temperature measurement and compromises the system's ability to protect the compressor from overheating.
Häufige Ursachen
- Discharge thermistor (49C) is shorted or open.
- Faulty temperature sensor in the discharge line.
- Wiring fault to the discharge thermistor.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Measure the resistance of the discharge thermistor at its leads — compare to a resistance-temperature chart if available.
- 2
Inspect the thermistor's wiring and connector on the outdoor unit PCB for damage, corrosion, or secure seating.
- 3
Verify the thermistor is correctly seated and making good thermal contact with the compressor discharge pipe.