UF

Compressor Overcurrent (Locked Start-up or Operation)

Mitsubishi Electric · R410A Systems

Was bedeutet UF ?

The compressor drew excessive current either during startup (locked rotor during start-up) or during ongoing operation (operating locked). Both conditions indicate a severe mechanical failure or an electrical issue preventing the compressor motor from rotating freely.

Häufige Ursachen

  • Compressor overcurrent during start-up or operation.
  • Locked rotor condition.
  • Motor failure or excessive winding resistance.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure compressor running current on all three phases using a clamp meter — observe if it spikes before tripping.

  2. 2

    Measure winding resistance of the compressor motor phases (U-V, V-W, U-W) and to ground using an ohmmeter.

  3. 3

    Verify correct voltage supply to the compressor terminals during startup attempt.

  4. 4

    If applicable, check the start capacitor value and Equivalent Series Resistance (ESR) using a capacitor meter.