0x00D1
Option Board Error
Omron · CJ-series CJ2 CPU Unit
Was bedeutet 0x00D1 ?
An Option Board error has occurred, indicated by A315.13 and A402.00. This typically happens if the Option Board was removed while the system was operating, if the board itself has failed, or if the connector mating is poor, leading to a loss of its specific functionality.
Häufige Ursachen
- The Option Board was physically removed while the system was operating.
- The Option Board has experienced a failure.
- Poor mating or improper connection of the Option Board connector.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check the mating of the Option Board connector.
- 2
Reconnect the Option Board connector firmly.
- 3
If the Option Board still fails after re-connection, replace the Option Board.