0x0300-0x035F or 0x03FF
Special I/O Unit Error
Omron · CJ-series CJ2 CPU Unit
Was bedeutet 0x0300-0x035F or 0x03FF ?
An error occurred during data exchange between the CPU Unit and a Special I/O Unit, indicated by A402.06 and A418 to A423. This signifies a communication failure or an internal fault within one of the Special I/O Units (unit numbers 0 to 95).
Häufige Ursachen
- Communication failure between the CPU Unit and a Special I/O Unit.
- Internal error within a specific Special I/O Unit.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check the specific Special I/O Unit indicated by A418 to A423.
- 2
Refer to the affected Unit's operation manual for detailed troubleshooting steps.
- 3
Restart the Unit by toggling its Restart Bit or by cycling its power OFF and ON again.
- 4
If the Unit does not restart or the error persists, replace the Special I/O Unit.