I/O Bus Error
Omron · CJ-series CJ2 CPU Unit
Was bedeutet 0x80C0 to 0x80C7, 0x80CE, or 0x80CF ?
An error has occurred in the communication bus line between the CPU and I/O Units, or the End Cover is not correctly connected to the CPU Rack or an Expansion Rack. This is a fatal error, indicated by flag A401.14. Auxiliary Area A404 contains the error slot number (00 to 09, with '0F hex' for undetermined slot, '0B hex' for built-in EtherNet/IP port bus error) and rack number (00 to 03, with '0E hex' for missing End Cover).
Häufige Ursachen
- Fault in the bus line cable between the CPU and I/O Units or between Racks.
- End Cover is not connected to the CPU Rack or an Expansion Rack.
- Damage to the I/O bus cable or the I/O Units themselves.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Cycle power OFF and ON again to the PLC system.
- 2
If the error persists, turn power OFF and physically check all cable connections between I/O Units and Racks, and verify End Covers are securely connected.
- 3
Inspect I/O bus cables and I/O Units for any signs of physical damage.
- 4
Cycle power OFF and ON again to the Rack's power supply.