Frequency Upper Limit Exceeded
Omron · MX2 Inverter
Was bedeutet 001 ?
This warning indicates that the parameter set for the frequency upper limit (A061) is configured to a value higher than the inverter's maximum allowed frequency (A004). This inconsistent setting may lead to unexpected operational limits or prevent the drive from reaching its full potential.
Häufige Ursachen
- Inadvertent manual input of A061 (Frequency Upper Limit) to a value greater than the drive's inherent maximum frequency (A004).
- Software bug or corrupted parameter memory leading to an incorrect default value for A061 after a reset or firmware update.
- Restoration of an incompatible parameter backup from a different drive model with a higher A004 setting.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Access parameter A061 (Frequency Upper Limit) and compare its value to A004 (Inverter Max Allowed Frequency).
- 2
Set A061 (Frequency Upper Limit) to a value equal to or less than A004 (Inverter Max Allowed Frequency). A common practice is to set A061 to match A004 for maximum allowable speed.
- 3
Confirm that the new setting for A061 is stored by powering the drive off and on, then verifying the parameter value again.
- 4
If the issue persists, perform a parameter reset to factory defaults (e.g., P0-01 set to "99") and then re-enter all necessary application parameters carefully.