Übersetzen...
E37.

Emergency Shutoff

Omron · MX2 Series Type V2 Compact Inverter

Was bedeutet E37. ?

An emergency shutoff fault is triggered when the safety input terminals GS1/GS2 are activated, initiating a protective shutdown of the inverter. This is a critical safety response, indicating that an external emergency stop device or safety system has detected a hazardous condition and commanded the inverter to cease operation immediately.

Häufige Ursachen

  • Activation of an external safety device (e.g., E-stop button, safety light curtain, safety gate switch) connected to the GS1/GS2 safety input terminals.
  • Short circuit or wiring fault in the safety circuit connected to GS1/GS2, causing an unintended activation of the safety input.
  • Malfunction of an internal safety relay or associated safety monitoring circuit within the inverter itself, falsely triggering the safety shutdown.
  • Incorrect parameter setting for the safety inputs, such as A1-01 (Safety Input Configuration) not matching the actual external safety circuit wiring.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Identify and inspect all external safety devices connected to the GS1/GS2 safety input terminals. Confirm their current state (e.g., E-stop released, gate closed).

  2. 2

    Measure the voltage/continuity across the GS1/GS2 terminals at the inverter input, verifying the safety circuit's integrity according to the inverter's safety manual (e.g., 24VDC high for safety active).

  3. 3

    Disconnect all external wiring from GS1/GS2. If the fault clears, the issue is with the external safety circuit or its wiring.

  4. 4

    Verify parameter A1-01 (Safety Input Configuration) matches the actual external safety circuit wiring (e.g., 1-channel or 2-channel input, NC/NO contacts).

  5. 5

    If the fault persists with external wiring disconnected and parameters are correct, the internal safety circuit or control board may be defective and require replacement.

Alle Codes in diesem Handbuch durchsuchen (41)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Omron MX2 Series Type V2 Compact Inverter