No Origin Input Signal
Omron · SYSMAC CJ Series PLC
Was bedeutet 0201 ?
This fault occurs during an origin search when the main origin input signal was not received. This prevents the system from precisely determining its home position, indicating a failure to detect the final origin marker.
Häufige Ursachen
- Faulty wiring of the origin input signal, leading to an open circuit or poor connection.
- Incorrect 'Origin Input Signal Type' (NC or NO) configured in PLC Setup.
- Origin sensor failure, damage, or mispositioning, preventing proper detection.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Visually inspect the wiring connections for the origin input signal for integrity; measure continuity of the cable from sensor to input terminal.
- 2
Access the PLC Setup 'I/O Module Tab Page' using CX-Programmer and verify the 'Origin Input Signal Type' setting is correctly configured (NC or NO) to match the sensor's operation.
- 3
Test the origin input sensor operation by manually activating it and verifying the corresponding input signal status at the PLC input terminal.
- 4
Ensure the physical positioning of the origin input sensor allows for proper detection during an origin search.
- 5
Initiate an origin search again from the HMI or programming software.