Pulse Output 3 Interrupt Feeding Error
Omron · SYSMAC CJ Series PLC
Was bedeutet A327.09 ?
This flag activates if the Pulse Value (PV) for pulse output 3 experiences an overflow or underflow while an interrupt input is received, or during the execution of the IFEED(892) instruction when a specified number of pulses is being moved and the origin is defined. This indicates a data integrity issue within the pulse counter, specifically during interrupt-driven feeding operations where the PV limits are exceeded.
Häufige Ursachen
- PV overflow or underflow occurred during an interrupt input event while IFEED(892) instruction for pulse output 3 was active.
- PV overflow or underflow occurred while the specified number of pulses was being moved by the IFEED(892) instruction for pulse output 3, with the origin defined.
- The specified number of pulses in the IFEED(892) instruction for pulse output 3 was too large, causing the PV to exceed its 32-bit range.
- Conflicting or poorly timed interrupt inputs while the IFEED(892) instruction for pulse output 3 is running.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Examine the ladder program logic related to the IFEED(892) instruction and associated interrupt inputs for pulse output 3.
- 2
Confirm that the specified number of pulses for the IFEED(892) instruction for pulse output 3 will not cause the PV to exceed the 32-bit range.
- 3
Analyze the timing of interrupt inputs relative to IFEED(892) execution for pulse output 3 to prevent concurrent actions leading to PV over/underflow.
- 4
Stop and then restart the IFEED(892) instruction processing for pulse output 3 to clear the flag.
- 5
Execute the INI(880) instruction for pulse output 3 to change (reset) its PV.
- 6
Toggle the Pulse Output 3 Reset Bit A543.00 from OFF to ON to clear the PV for pulse output 3 (documented on page 183).