405

SAFETY CIRCUIT FAULT

Otis · DSD 412 DC Elevator Drive

Was bedeutet 405 ?

The Safety Circuit, wired between TB3-1 and TB3-6 on Power Supply A4, was not closed for 100 milliseconds before a “Drive Run” command, or it opened unexpectedly while the loop contactor was closed.

Häufige Ursachen

  • Safety Circuit between TB3-1 and TB3-6 not closed before a “Drive Run” command.
  • Safety Circuit opened unexpectedly while the loop contactor was closed.
  • Intermittent connections in the Safety Chain.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify that the Safety Circuit between TB3-1 and TB3-6 on Power Supply A4 is properly closed.

  2. 2

    Check for intermittent connections in the Safety Chain.

  3. 3

    Ensure the Safety Chain remains closed for 100ms prior to and during a “Drive Run” command.