Übersetzen...
-

Selftest Not Successfully Finished

Otis · GAA21750AK3 Service Tool

Was bedeutet - ?

This code indicates that one or more internal selftests of the LCB_II board's memory (EPROM, EEPROM, RAM) or the Remote Serial Link (RSL) did not complete successfully. A failed selftest can signify a hardware fault, leading to unreliable or non-operational system behavior for the GAA21750AK3 service tool.

Häufige Ursachen

  • Faulty EPROM, EEPROM, or RAM memory on the LCB_II board.
  • Issues with the Remote Serial Link (RSL) communication or module.
  • For a new EEPROM, the first test run may result in a failure until checksum verification is established.
  • Memory address out of RAM area.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Run the selftest multiple times using the GAA21750AK3 service tool to confirm the failure is consistent.

  2. 2

    Observe the flashing question mark on the display to identify which specific sub-test (PR EPROM, EE EEPROM, RA RAM, RS Remote Serial Link) is failing.

  3. 3

    If the EEPROM test fails on its initial run with a new EEPROM, run it again after the first write operation.

  4. 4

    Inspect RSL connections and the associated module if the RS test (Remote Serial Link) fails.

  5. 5

    Check for correct memory addresses if configuring memory content, ensuring they are within valid RAM boundaries.

Alle Codes in diesem Handbuch durchsuchen (15)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes