Übersetzen...
1

Cross-circuit in Sensor Circuit 2

Phoenix Contact · ib il safe 2-eco

Was bedeutet 1 ?

A cross-circuit has been detected in sensor circuit 2, indicated by active cross-circuit detection. This condition occurs while sensor circuit 1 is active, the reset/start circuit is activated, and the segment circuit is open. This type of error can compromise the functional safety of the device by providing incorrect sensor input information.

Häufige Ursachen

  • Cross-circuit detected within sensor circuit 2

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Switch off the operating voltage to the device

  2. 2

    Identify and physically remove the cross-circuit in sensor circuit 2

  3. 3

    Perform a function test to verify correct device operation

Alle Codes in diesem Handbuch durchsuchen (8)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Phoenix Contact ib il safe 2-eco