Übersetzen...
F010

Overcurrent

Schindler · Easy Altivar ATV310 Drive

Was bedeutet F010 ?

For the ATV310 drive, this fault indicates that the current drawn by the motor has exceeded the drive's maximum permissible current limit. This is often caused by incorrect motor control parameters, an excessively high load or inertia, or mechanical binding in the driven system.

Häufige Ursachen

  • Incorrect parameters set in the Motor control menu (300-) for the connected motor or application
  • Inertia or mechanical load of the application is too high for the motor/drive combination
  • Mechanical locking or binding in the driven system, preventing free movement
  • High switching frequency (parameter 315) causing increased current ripple or losses
  • Issues with the ground connection of the drive, motor cable, or motor insulation causing leakage currents

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check and verify all parameters in the Motor control menu (300-) against the motor nameplate and application requirements.

  2. 2

    Check the sizing of the motor, drive, and mechanical load to ensure they are appropriate for the application.

  3. 3

    Inspect the mechanical system for any signs of binding, blockage, or locking that could cause high motor current.

  4. 4

    Connect line motor chokes on the input side of the drive if not already present, to reduce current harmonics and transients.

  5. 5

    Reduce the Switching frequency range (parameter 315) if it is set too high for the application.

  6. 6

    Check the ground connection of the drive, motor cable, and motor insulation for short circuits or ground faults.

Alle Codes in diesem Handbuch durchsuchen (37)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Schindler Easy Altivar ATV310 Drive