F013

Motor overload

Schindler · Easy Altivar ATV310 Drive

Was bedeutet F013 ?

The drive displays an F013 fault when the Motor thermal state (808) exceeds 118%. This indicates that the motor is operating beyond its safe thermal limits, risking damage to the motor windings.

Häufige Ursachen

  • The motor's thermal state (808) has exceeded 118% of its rated thermal capacity.
  • Excessive mechanical load on the motor, leading to higher than normal current draw.
  • Insufficient cooling for the motor, such as blocked ventilation fins or a malfunctioning motor fan.
  • Incorrect motor nameplate data or overload protection parameters configured in the drive.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Reduce the mechanical load on the motor to bring its operating current within safe limits.

  2. 2

    Check the motor's cooling system for proper operation, clear any obstructions from cooling fins, and ensure adequate airflow around the motor.

  3. 3

    Monitor the Motor thermal state (808) parameter in the Monitoring mode (MOn) to observe the motor's thermal condition.

  4. 4

    Verify that all motor parameters in the drive (e.g., motor nominal current, motor overload curve) accurately match the motor's nameplate data.

  5. 5

    Allow the motor to cool down before attempting to restart the drive.