Übersetzen...
F031

Incorrect configuration

Schindler · Easy Altivar ATV310 Drive

Was bedeutet F031 ?

This fault indicates that the drive's configuration is inconsistent. It can occur if an HMI block from a drive with a different rating is installed, or if the customer parameters currently loaded are not valid for the drive.

Häufige Ursachen

  • HMI block replaced by an HMI block configured on a drive with a different rating.
  • The current configuration of customer parameters is inconsistent or corrupted.
  • Configuration data integrity issue during power-up or parameter changes.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Return the drive to its factory settings to clear any inconsistent configuration data.

  2. 2

    Retrieve and load a valid backup configuration if one is available and known to be compatible.

  3. 3

    If the fault persists after reverting to factory settings, contact your local Schneider Electric representative for further assistance.

Alle Codes in diesem Handbuch durchsuchen (37)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Schindler Easy Altivar ATV310 Drive