Communication Interruption (Keypad)
Schneider Electric · Altistart 22 Soft Starter
Was bedeutet COME ?
The communication link between the remote keypad and the soft starter has been interrupted. This message flashes after 20 retries within a 50 ms timeout, indicating a loss of connection.
Häufige Ursachen
- Loose or disconnected ribbon cable/communication cable connecting the remote keypad to the soft starter's communication port.
- Excessive electromagnetic interference (EMI) disrupting the communication signals between the keypad and soft starter.
- Faulty remote keypad unit or soft starter's communication port hardware.
- Incorrect keypad connection or usage of a non-compatible cable length or type.
- Physical damage to the communication cable (e.g., crushing, cut, broken conductor).
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
1. Power down the soft starter, then carefully inspect and re-seat the communication cable connecting the keypad to the soft starter.
- 2
2. Check the communication cable for any visible damage, cuts, or crushed sections and replace it with an identical, compatible cable if necessary.
- 3
3. Ensure the communication cable is routed away from power cables or other sources of high electromagnetic interference (EMI).
- 4
4. Test communication with a known good, compatible remote keypad to rule out a faulty keypad unit.
- 5
5. Measure voltage levels on the communication lines (e.g., 5VDC, data lines) at both ends of the cable to check for signal integrity.