Process Underload Fault (Torque)
Schneider Electric · Altivar Machine ATV320 Variable Speed Drive
Was bedeutet ULF ?
A torque underload detected fault. This indicates that the motor is operating with significantly less load than expected, potentially pointing to a mechanical failure (e.g., broken belt, pump cavitation) or a material flow issue. While not immediately damaging, it signals an abnormal process condition.
Häufige Ursachen
- Loss of mechanical load on the motor (e.g., broken belt, coupling failure, pump cavitation, fan blade damage).
- Underload detection threshold (e.g., Parameter P1-25) set too high or delay time (P1-26) too short.
- Incorrect motor parameters programmed into the drive, leading to an inaccurate torque estimate.
- Sensor failure or poor calibration if external torque/load feedback is used.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
1. Inspect the mechanical connection between the motor and the driven equipment for belts, couplings, or gears.
- 2
2. Monitor the drive's output current (e.g., display parameter d0-02) or estimated torque to assess actual load.
- 3
3. Adjust the underload threshold parameter (e.g., P1-25) to a level appropriate for the application's normal minimum load.
- 4
4. Verify the underload delay time parameter (e.g., P1-26) is long enough to ride through normal load fluctuations.
- 5
5. Confirm motor nameplate data (P0-01 to P0-10) is correctly entered, as this affects torque estimation accuracy.