AC Output Over Voltage
Schneider Electric · XW Pro NA Operation Guide
Was bedeutet F2 ?
This Escalating Automatic Fault indicates an AC over-voltage shutdown (above 135 V). If it occurs 3 times in 30 seconds, it becomes a manual fault, meaning the inverter has repeatedly shut down to protect connected loads.
Häufige Ursachen
- Regenerative load (e.g., crane, elevator) feeding power back into the inverter, causing DC bus and then AC output over-voltage.
- Over-sizing of inverter for a small load, leading to poor voltage regulation under light load conditions.
- Faulty voltage regulation circuit or output stage components within the inverter.
- Improperly configured inverter output voltage settings (e.g., parameter P3-10 set too high above 135V).
- Utility grid over-voltage condition feeding back into grid-tied inverter systems.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Measure AC output voltage at inverter terminals L1, L2, L3 (or L1, N) using a true RMS multimeter under no-load and full-load conditions.
- 2
Verify inverter output voltage configuration (e.g., Parameter P3-10, P3-11) is set correctly for the application's nominal voltage (e.g., 120V or 240V).
- 3
Check for regenerative load conditions and verify proper functioning of braking resistors or regeneration units (e.g., measure resistance of braking resistor).
- 4
Monitor utility grid voltage at the inverter input terminals (L1, L2, L3, N) to confirm it remains below 135V nominal.
- 5
Perform a factory reset of inverter parameters (e.g., Parameter P0-01 to "Reset") and reconfigure essential settings to eliminate configuration errors.