Übersetzen...
F35

AI L2 Under Voltage

Schneider Electric · XW Pro NA Operation Guide

Was bedeutet F35 ?

This fault indicates an L2 under-voltage condition (108 V) detected by the anti-islanding protection, triggering a slow disconnect. This mechanism ensures the inverter disconnects from an unstable grid, protecting both the inverter and grid from potential damage due to insufficient voltage.

Häufige Ursachen

  • Grid L2-Neutral voltage dropping below 108 V for a sustained period, indicating persistent grid brownout or heavy load drawing power from phase L2.
  • Undersized utility grid connection or long feeder cables causing significant voltage drop on phase L2 under normal operating loads.
  • Inverter's L2 voltage sensing circuit experiencing a degradation in accuracy or intermittent measurement loss over time.
  • Anti-islanding parameter P_AI_L2_Volt_Min_Slow set too high, triggering disconnects on minor, acceptable voltage dips.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Using a true RMS multimeter, continuously monitor the L2-Neutral voltage at the inverter's AC input terminal L2 over several hours to detect persistent low voltage.

  2. 2

    Compare the sustained L2-Neutral voltage readings against the specified 108 V trip threshold and the inverter's P_AI_L2_Volt_Min_Slow parameter.

  3. 3

    Verify the tightness and condition of the L2 phase and neutral conductor connections at the inverter's input terminals (e.g., Terminal L2, Terminal N).

  4. 4

    Investigate the local grid connection for other large loads drawing power from phase L2 that might cause voltage sags, especially during startup.

  5. 5

    If external voltage is stable, verify the inverter's internal L2 voltage measurement offset parameter (e.g., P_AI_L2_Volt_Offset) for potential misconfiguration.

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Schneider Electric XW Pro NA Operation Guide