110

Ex-e protection

SEW Eurodrive · Drives

Was bedeutet 110 ?

The MOVIMOT drive was operated at a setpoint speed below 5 Hz for more than 60 seconds. This violates the requirements for Ex-e protection, which demands a minimum operating speed to ensure safe operation in potentially explosive atmospheres.

Häufige Ursachen

  • MOVIMOT operated at a setpoint speed below 5 Hz for more than 60 seconds

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Increase the drive setpoint speed above 5 Hz

  2. 2

    Reset the error by cycling the DC 24 V supply voltage (off then on)

  3. 3

    Reset the error using the appropriate control method