Übersetzen...
91

Communication timeout bus module – MOVIMOT®

SEW Eurodrive · Drives

Was bedeutet 91 ?

The communications link between the fieldbus interface (MFP/MFI) and the MOVIMOT® inverter is interrupted or experiences a timeout. This system fault is signaled to the PLC as error code 91 dec via the diagnostics channel or status words, and typically triggers a steady 'SYS-F' LED light on the fieldbus interface.

Häufige Ursachen

  • Interrupted or faulty electrical communication link between the fieldbus interface (MFP/MFI) and the MOVIMOT® inverter.
  • Missing 24 V supply to the MOVIMOT® inverter.
  • Maintenance switch on the field distributor is set to OFF.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check and re-establish the electrical communication link between the fieldbus interface (MFP/MFI) and the MOVIMOT® inverter (e.g., verify connections at terminals RS+ and RS-).

  2. 2

    Verify the 24 V electronics supply voltage to the MOVIMOT® inverter.

  3. 3

    Check the setting of the maintenance switch on the field distributor to ensure it is in the ON position.

Alle Codes in diesem Handbuch durchsuchen (39)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes