Übersetzen...
F36

Option missing

SEW Eurodrive · MOVITRAC 07B System

Was bedeutet F36 ?

An option card is either incorrect, missing, or has incompatible settings for its setpoint source, control signal, or operating mode. This fault indicates a configuration mismatch or hardware absence, leading to an immediate switch-off with inhibit.

Häufige Ursachen

  • Installation of an unsupported or incorrect type of option card
  • Setpoint source, control signal source, or operating mode parameters are incompatible with the installed option card
  • Required option card (e.g., FBG11B, FIO12B, FIO21B) is not present
  • Front module FIO21B is not supplied with power

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Install the correct type of option card for the application.

  2. 2

    Verify parameters for setpoint source, control signal source, and operating mode are compatible with the installed option card.

  3. 3

    Check parameters P120 and P121 for general option card configuration.

  4. 4

    If FBG11B is used, check parameter P121. If FIO12B is used, check P120 and P642.

  5. 5

    If FIO21B is installed, set parameter P808 to "On" or supply the basic unit with external 24V.

Alle Codes in diesem Handbuch durchsuchen (41)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: SEW Eurodrive MOVITRAC 07B System