Übersetzen...
A05003

Power unit: Internal overtemperature

Siemens · DCM

Was bedeutet A05003 ?

This alarm signifies that the internal temperature within a chassis power unit has reached its alarm threshold. If the temperature increases by an additional 5 K, it will escalate to fault F30036, leading to a shutdown. It's crucial to address this to prevent potential damage and ensure continued operation.

Häufige Ursachen

  • Restricted cooling airflow due to dust accumulation on heat sinks, blocked ventilation openings, or dirty air filters.
  • Ambient temperature inside the control cabinet exceeding the drive's specified maximum operating temperature (e.g., above 50°C).
  • Reduced performance or partial failure of an internal cooling fan (e.g., decreased RPM, bearing noise) leading to inadequate heat dissipation.
  • Continuous operation at or above the drive's rated output current (P0307) for extended periods without sufficient cooling margin.
  • Improper control cabinet design leading to re-circulation of hot air or insufficient overall cabinet ventilation.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Monitor the drive's internal temperature sensors (e.g., r0035 for IGBTs, r0036 for heat sink) via diagnostics.

  2. 2

    Inspect and thoroughly clean the power unit's heat sink fins, air intake vents, and air filters using dry compressed air.

  3. 3

    Verify the actual ambient temperature inside the control cabinet using a calibrated thermometer; improve cabinet ventilation if necessary.

  4. 4

    Check the operating speed (e.g., r0032) and audible performance of the internal cooling fans for any signs of degradation.

  5. 5

    Reduce the drive's output load (e.g., via P1082) or adjust application cycle times to lower average current (r0027).

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes