F01001

FloatingPoint exception

Siemens · DCM

Was bedeutet F01001 ?

An exception, such as an invalid operation, division by zero, overflow, underflow, or imprecise result, occurred during a FloatingPoint data type operation. This error can originate from the base system or a specific application like FBLOCKS or DCC. The fault value (r0949) and r9999 provide detailed information about the cause and program counter at the time of the exception, indicating a critical calculation error.

Häufige Ursachen

  • Attempted division by zero in internal control algorithms, potentially caused by a parameter set to 0 when it should not be (e.g., a speed reference denominator).
  • Calculation resulting in an extremely large (overflow) or small (underflow) number that exceeds the FloatingPoint representation limits.
  • Incorrectly scaled feedback values (e.g., encoder signals, analog inputs) leading to out-of-range inputs for internal calculations.
  • Corruption of internal data or program memory, causing incorrect FloatingPoint operations to be performed.
  • Firmware bug related to specific calculation routines under certain operating conditions.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Perform a power cycle of the drive system (turn off, wait 30 seconds, turn on).

  2. 2

    2. Back up parameters, then execute a factory reset (P0010 = 30, P0970 = 1) and carefully re-enter/restore configuration.

  3. 3

    3. Review all parameters related to scaling, limits, and feedback (e.g., P0408 (Encoder pulses), P0076 (Analog input scaling)) for valid non-zero values where appropriate.

  4. 4

    4. Update the drive's firmware to the latest stable version.

  5. 5

    5. If the fault persists after all software and parameter checks, consider replacing the Control Unit due to potential hardware calculation unit failure.