Drive: Motor blocked
Siemens · DCM
Was bedeutet F07900 ?
The motor has been operating at its torque limit for an extended period while remaining below a defined speed threshold, indicating a mechanical blockage or severe overload. This could also be caused by speed oscillations at the controller limit or thermal derating of the power unit. Continued operation in this state can lead to motor overheating, mechanical damage, or damage to the drive.
Häufige Ursachen
- Mechanical obstruction in the driven machinery (e.g., jammed conveyor, seized bearing, foreign object in gear train).
- Excessive static or dynamic load exceeding the motor's and drive's torque capability (e.g., material jam in a processing machine).
- Incorrect motor parameters (e.g., P1-04 motor rated current, P1-07 motor no-load current) causing the drive to misinterpret current.
- Incorrect threshold settings for the motor blocked supervision function (e.g., P3-01 motor blocked speed threshold, P3-02 motor blocked time delay).
- Faulty motor encoder feedback (if used for speed monitoring) giving an erroneous low-speed reading while the motor attempts to move.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Visually inspect the mechanical system connected to the motor shaft for any obstructions, jamming, or excessive friction.
- 2
Manually attempt to turn the motor shaft or driven equipment (with power off) to assess mechanical resistance.
- 3
Check drive parameters P1-04 (Motor rated current), P1-05 (Motor rated speed), and P1-07 (Motor no-load current) against the motor nameplate.
- 4
Verify the motor blocked supervision parameters, such as P3-01 (Speed threshold below which it's considered blocked) and P3-02 (Time delay before fault).
- 5
Measure motor current (e.g., at U, V, W phases) and compare to the drive's current limit (P1-03) while attempting to start the motor.
- 6
If an encoder is used, check encoder feedback signals (e.g., A/B phases) at the drive's input terminals for proper pulse generation and noise immunity.