PROFIBUS: wrong PB address at startup
Siemens · SINAMICS G120
Was bedeutet A00707 ?
The PROFIBUS address configured for the drive is incorrect at startup, either due to an improper DIP switch setting or an incorrect value in parameter P0918. This prevents the drive from communicating correctly on the PROFIBUS network, leading to a loss of control from the PROFIBUS master.
Häufige Ursachen
- PROFIBUS address DIP switch (if applicable) incorrectly set, conflicting with P0918 or the master's configuration.
- Parameter P0918 (PROFIBUS address) set to a value that does not match the master's configuration for the drive.
- Multiple devices on the PROFIBUS network configured with the exact same address (address collision), preventing unique identification.
- Loss of non-volatile memory on the drive causing P0918 to revert to a default or incorrect value upon power cycle.
- Incorrect bus configuration in the PROFIBUS master's software, assigning a different address than physically set on the drive.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
1. Check the physical DIP switch settings on the PROFIBUS module (if present) and ensure they correspond to the desired PROFIBUS address.
- 2
2. Verify parameter P0918 (PROFIBUS address) in the drive and ensure it precisely matches the address configured in the PROFIBUS master's hardware configuration.
- 3
3. Review the PROFIBUS network's address map to confirm no other device is assigned the same address as the drive.
- 4
4. Perform a factory reset of communication parameters (e.g., P0010=30, P0970=1) and then reconfigure P0918 to ensure correct storage.
- 5
5. Cycle power to the drive and observe the PROFIBUS status LEDs (e.g., BF) during startup for address recognition status.