Übersetzen...
F01649

Internal software error

Siemens · SINAMICS G120

Was bedeutet F01649 ?

This fault indicates an internal software issue, likely a buffer overflow during checksum calculations for parameter access or an endless safety loop within the P1 or P2 processors. Errors with r0949 > 100 are for Siemens internal diagnostics. This is a critical internal system error that requires specialized attention.

Häufige Ursachen

  • Firmware bug within the drive's operating system, potentially triggered by a specific operational sequence or parameter combination.
  • Memory corruption within the drive's control unit caused by unstable power, severe EMI, or component aging.
  • Hardware watchdog timer fault on the main control board, indicating a processor lock-up (P1 or P2).
  • Extensive parameter changes or frequent parameter writes leading to buffer overflow during checksum calculation or data storage.
  • Internal communication error between the drive's processors (P1 and P2) or safety-related modules, leading to an inconsistent state.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Power cycle the drive by disconnecting and reconnecting the main supply voltage, then observe if the fault clears on restart.

  2. 2

    2. Update the drive's firmware to the latest available version, as internal software errors are often resolved in later releases.

  3. 3

    3. Perform a factory reset (e.g., P0010=30, P0970=1) to clear all parameters and then reconfigure the drive from scratch, avoiding loading old parameter sets.

  4. 4

    4. Monitor the drive's internal diagnostic registers (e.g., r0949) for more specific sub-fault codes that can pinpoint the error.

  5. 5

    5. If the fault persists, replace the main control board, as this often indicates an internal hardware defect beyond software remediation.

Alle Codes in diesem Handbuch durchsuchen (109)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes