TM150 Temperature Fault Channel 4
Siemens · SINAMICS S120/S150 Reference List
Was bedeutet F35400 ?
This fault is triggered when the actual temperature (r4105[4]) for channel 4 on the Terminal Module 150 (TM150) exceeds its configured fault threshold (p4102[9]), or if an associated timer (p4103[4]) expires. If a BICO interconnection exists, this fault will cause the drive to shut down. The fault will persist until the temperature falls below the threshold (minus hysteresis) and is acknowledged.
Häufige Ursachen
- The component connected to TM150 channel 4 is experiencing a sustained overload, causing its temperature to surpass design limits.
- High ambient temperature surrounding the TM150 module or the monitored equipment, hindering efficient heat dissipation.
- Failure or significant degradation of the temperature sensor on channel 4, resulting in an inaccurate, high r4105[4] reading.
- Blocked cooling fins or a non-functional fan dedicated to cooling the TM150 module or the equipment monitored by channel 4.
- Parameter p4102[9] (Temperature fault threshold channel 4) is set improperly low for the actual operating environment or component.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Measure the actual operating temperature of the component monitored by channel 4 using a calibrated external device and compare it with r4105[4].
- 2
Inspect and clean any cooling fans, filters, and heat sinks associated with the TM150 module and the equipment on channel 4.
- 3
Verify the integrity and connection of the temperature sensor wiring for channel 4 from the sensor to the TM150 module.
- 4
Review the process load and operating cycle of the equipment connected to channel 4 to identify if it is exceeding its thermal capacity.
- 5
If the physical temperature is normal but r4105[4] indicates high, replace the temperature sensor connected to TM150 channel 4.
- 6
If analysis confirms safe operational temperatures are higher than the threshold, adjust parameter p4102[9] (Fault threshold channel 4) to an appropriate, safer value.