Übersetzen...
XFMR
Transformer Connected to Wrong Grid Configuration
SMA · SUNNY BOY 5000US-8000US Solar Inverter
Was bedeutet XFMR ?
The Sunny Boy SB50US-80US-IUS094030's internal transformer is incorrectly connected or configured for the present grid type. This issue can manifest in Delta corner-grounded grids if the grid ground is not connected to terminal L2, or in unbalanced 208V/240V grids if L1 and L2 are interchanged.
Häufige Ursachen
- Incorrect transformer connection to the grid.
- Grid ground not connected to terminal L2 in Delta corner-grounded grids.
- L1 and L2 interchanged in unbalanced 208V and 240V grids.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check the physical connection of the inverter's transformer to the grid terminals.
- 2
In Delta corner-grounded grids, ensure that the grid ground is correctly connected to terminal L2.
- 3
In unbalanced 208V and 240V grids, attempt interchanging the L1 and L2 connections to clear the error.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: SMA SUNNY BOY 5000US-8000US Solar Inverter